Technology

This standard is in strict accordance with GB / t18813-2014, and specifies the requirements, test methods, inspection rules, marks, packaging, transportation, storage and contract contents of copper strip for transformer. This standard is applicable to copper strip for winding transformer coil.


Table 1 brand, state and specification of strip

Brand

Supply status

Specifications

Thickness(mm)

Width(mm)

TU1,T2

M(060)

0.1~<0.50

≤820

0.503.50

≤820

Note: other grades, states and specifications can also be supplied after negotiation between the supplier and the supplier

 

Table 2 allowable deviation of strip thickness

Thickness

(mm)

Width(mm)

≤200

200400

400600

600820

Thickness tolerance

Ordinary grade

High precision

Ordinary grade

High precision

Ordinary grade

High precision

Ordinary grade

Higher level

0.10.20

0.010

0.010

0.010

0.200.30

0.015

0.010

0.020

0.010

0.020

0.010

0.300.50

0.020

0.015

0.025

0.020

0.030

0.020

0.500.70

0.030

0.025

0.035

0.030

0.040

0.035

0.050

0.040

0.701.10

0.035

0.030

0.040

0.035

0.045

0.040

0.060

0.050

1.101.50

0.045

0.040

0.045

0.040

0.050

0.045

0.070

0.050

1.502.50

0.050

0.045

0.055

0.050

0.070

0.060

0.090

0.080

>2.50~3.00

0.055

0.050

0.060

0.055

0.080

0.070

0.100

0.090

 

Table 3 width of strip and allowable deviation of width

Width

Thickness

≤1.0

1.01.5

1.52.5

Thickness tolerance

Ordinary grade

Higher level

Ordinary grade

Higher level

Ordinary grade

Higher level

≤100

0.20

0.10

0.30

0.20

0.40

0.25

100300

0.30

0.15

0.40

0.25

0.50

0.30

300820

0.50

0.30

0.60

0.40

0.60

0.50

Note: when the demander requires one-way deviation, the value should be twice of the value in the table.

 

Table 4 mechanical properties of strip 

Brand

State

Tensile strength 

Rm/MPa

Elongation 

A11.3/%

Vickers hardness

HV

TU1,T2

M(060)

195~260

≥35

4565

Note: for the strip with thickness less than 0.20 mm, the test results are for reference only.

 

Table 5 electrical properties of strip (20 ℃)

Brand

Conductivity/

%IACS

Resistance coefficient/

Ω·mm²/m

TU1

≥100

0.017 241

T2

98

0.017 593

Note: either conductivity or resistance coefficient shall be selected and indicated in the contract. If not specified, the conductivity shall be tested.
Conductivity = 100% × 0.017241 / measured value of resistance coefficient.